Model |
PE5108G |
Electrical |
Nominal Input Voltage |
100 – 240 VAC |
Maximum Input Current |
10A Max |
Input Frequency |
50-60 Hz |
Input Connection |
IEC 60320 C14 |
Input Power |
2300 VA(Max) |
Outlet Type |
Total: 8 x IEC320 C13 |
Nominal Output Voltage |
100 – 240 VAC |
Maximum Output Current (Outlet) |
C13 : 10A(Max) |
Maximum Output Current (Bank) |
10A(Max) |
Maximum Output Current (Total) |
10A(Max) |
Breakers |
1 x 15A Non-Fuse Breaker |
Metering |
Bank level Current, Voltage, VA , PF and KWh Monitoring |
Outlet Switching |
None |
Environment Sensor Ports |
2 |
Metering Accuracy |
Voltage Range: 100VAC ~ 250VAC +/-1% |
Power Range: 100W ~ Maximum Capacity +/- 2% |
Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1% |
Physical Properties |
Dimensions (L x W x H) |
TBD |
Weight |
TBD |
Power Cord Length |
3 m |
Environmental |
Temperature (Operating / Storage) |
0 – 50°C / -20 – 60°C |
Humidity (Operating & Storage) |
0 – 80% RH, Non-Condensing |
Compliance |
EMC Verification |
CE, Others by Request |
Safety Verification |
TUV-CB, CE-LVD, Others by Request |